Fault conditions cause of issue Method of exclusion Undrained Filter, launch duct, semi-float vent or drain nozzle blocked Cleaning Undrained Working pressure difference is exceeded, the float does not sink Change to the appropriate model Poor drainage Filter, radiator or drain nozzle blocked Cleaning Poor drainage Insufficient drain valve Change to the appropriate model Poor drainage Does not meet the trap pressure difference Change to the appropriate model leakage Bonnet gasket damage Tighten the bolt or replace the gasket leakage Semi-floating ball and drain nozzle are not sealed Remove the half float, apply the abrasive sand, and grind it against the nozzle until it fits well. Spray Nozzle is not sealed Grinding nozzle Spray The working pressure difference fluctuates too much and too fast, destroying the water seal inside the valve body Close the shut-off valve in front of the trap for 1-2 minutes, then slowly open it to resume normal operation. Spray Bypass valve failure Replace the bypass valve Dehydrated Carrot Without Sugar,Air-Dried Carrot Flakes,Dehydrated Carrot Flakes,Ad Carrot Flakes Xinghua Jiahe Foods Co., Ltd. , https://www.jiahefoods.com